ECOM America, Ltd.
1628 Oakbrook Drive
Gainesville, GA 30507

Toll Free 877.326.6411
TEL. 770.532.3280
FAX 770.532.3620

 


ECOM CL

 

BROCHURE

+ + + + +    

Standard Features

The ECOM CL package includes:

  • Condensation trap with fine dust filter
  • Electronic condensate monitoring
  • Temp. trend indication f. core stream search
  • CO switch-off without measurement
    interruption (opt.)
  • Fresh air purging by CO exceeding (opt.)
  • Fresh air purging after operation
  • Fine dust filter at condensation trap
  • Soot filter along sampling tubing
  • Battery 6V and 110V Charger at 60 Hz (230v/50hz)
  • ECOM CL The ECOM-CL is an easy to use gas analyzer designed for basic combustion monitoring in a variety of applications. The CL is fitted with up to 3 gas sensors, measuring O2, CO & NO, plus Stack and Ambient Temperatures, and Stack Pressure & Draft. The CL also calculates CO2, Efficiency, Losses, Excess Air and Oxygen correction 0-20%. The instrument is housed in a robust composite case suitable for rugged field use. On board data storage for up to 500 separate readings. An IR printer port transmits data to a portable printer for on-the-spot print-outs. The onboard computer has 5 pre-programmed fuel types and can store up to 16 programmable as well as a 60 second calibrationtime. The ECOM-CL sample conditioning system consists of a high flow pump and radiant gas cooler with moisture trap. An automatic shut-off activates when the gas cooler filter becomes saturated. Another unique feature of the CL is an Automatic and Manual CO bypass function which protects the CO sensor from over exposure.

    • TECHNICAL SPECS
    • close tab
    MEASUREMENT (KEY) RANGE ACCURACY RESOLUTION SENSOR TYPE  
    Oxygen (O) 0-21% ± .03% vol% 0.1% vol. Electrochemical  
    CO ppm, n. H2-comp. 0-2,000 ppm ± 20 ppm 1 ppm Electrochemical  
    CO ppm, H2-comp. (opt.) 0-4,000 ppm   1 ppm Electrochemical  
    Nitric Oxide (opt.) 0-5,000 ppm ± 5% Measured 1 ppm Electrochemical  
    Gas Temperature 0-932° F ± 2% Measured 1 deg F NiCrNi  
    Ambient Temperature 0-210 F ± 2% Measured 1 deg F Semi-Conductor  
    Draft / Pressure ± 20 hPa ± 2% Measured 0.1% hPa DMS  
    O2 Correction 0-20% Oxygen        
    Carbon Dioxide (CO2) 0-CO2 max of fuel Calculated      
    Efficiency 0-99.9% Calculated      
    Exxess Air (Lambda) <1 Calculated      
               
    *ACCURACY: When calibrated prior to use per ECOM America, Ltd. specifications.
     
    PHYSICAL Dimensions: ≈ 15 x 10 x 8 inches.
    Weight: 10.14 lbs. complete with sampling system
     
    ELECTRICAL Batteries: 6V / 3.8 Ah
    Charger: 110/220V 50/60Hz
    Cable Length: 72”
    Display: Backlit, adjustable contrast & zoom
     
    OPERATING TEMPERATURE Tolerated Ambient Temperature: +5° - +40° C
    Tolerated Storage Temperature : -20° - +50° C